SPECIFICATIONS:
- CAB OPTIONS
- Sierra
- Executive
- Plantation,
- Presidential
- PLATFORM: Cab platform is constructed of 1 1/4" unfinished oak veneer plywood.
- LIGHTING: Lighting will consist of two (2) recessed ceiling lights operated on a separate 10-volt circuit.
- CAR DOOR: Each open side of cab shall be equipped with a folding car door with (3) clear acrylic center panels and a finish that matches selected car finish.
- DOOR INTERLOCKS: A hoistway door interlock shall be furnished for each hoistway entrance. Interlock shall prevent operation unless doors are closed and prevent opening of door when car is not at that landing.
- OPERATION: Operation shall be automatic.
- Each entrance has a call station.
- The push-button station in the car has one button for each level served.
- The push-button station in the car has an emergency stop button, alarm button, and light switch.
- Alarm bell is installed on top of car.
- GUIDE RAILS: Guide rails are mounted to the floor slab and hoistway wall with steel brackets.
- MACHINE: Machine is a 1:2 roped hydraulic type consisting of a constant displacement, submersible pump and motor, oil reservoir and hydraulic control unit. The power is equipped with battery operated controlled descent, which lowers the lift to the lowest landing in the event of power failure.
- CARRIAGE: Carriage is attached to the car platform on the guide rail side of the car.
- SAFETY: Instantaneous broken cable device shall be provided on the carriage.
- ELECTRIC SUPPLY: Shall be 220 volt, single phase, 30 amps, or 220 volt, three phase, 60 hertz, 30 amps.
- CONTROLLER: Controller shall be programmable, solid state located in the machine room. Auto call, single floor register operation shall be provided.
ELEVATOR SHAFT REQUIREMENTS.
- Suitable, legal, two-hour fire-rated hoistway, if consistent with building Construction.
- Pit floor to be designed for an impact load of 3500 pounds.
- Suitable, fire rated hinged hoistway entrance doors and machine access doors.
- Separate machine room with an entrance door.
- 220 volt single-phase power supply with a line disconnect switch immediately adjoining the control cabinet, and within sight of the machine.
- A separate 120 volt 20 amp single-phase power with fused disconnect switch or circuit breaker with feeder wiring to controller.
- A light fixture and a 110-volt outlet must be provided in the machine area. The switch for operation of the light fixture must be located in the machine room by the access door.
- Connection of telephone traveling cable to outside central exchange, as required by ANSI A17.1 CODE.